APC Smart-UPS RT 20kVA RM 230V - SURT20KRMXLI

Reference: SURT20KRMXLI

Manufacturer:

APC Smart-UPS RT 20kVA RM 230V - SURT20KRMXLI
Model:
SURT20KRMXLI

APC Smart-UPS RT, 16 kW / 20 kVA,Input 230V / Output 230V, Interface Port DB-9 RS-232, RJ-45 10/100 Base-T, Smart-Slot, Extended runtime model, Rack Height 12 U

Includes: CD with software, Rack Mounting support rails, Smart UPS signalling RS-232 cable, User Manual, Web/SNMP Management Card

$ 21,099.00 tax excl.

Data sheet

UPS Type Smart-UPS
Rack Mountable Yes
UPS Orientation Rack
Power Rated VA 20000

More info

APC Smart-UPS RT 20kVA RM 230V - SURT20KRMXLI
Model:
SURT20KRMXLI

APC Smart-UPS RT, 16 kW / 20 kVA,Input 230V / Output 230V, Interface Port DB-9 RS-232, RJ-45 10/100 Base-T, Smart-Slot, Extended runtime model, Rack Height 12 U

Includes: CD with software, Rack Mounting support rails, Smart UPS signalling RS-232 cable, User Manual, Web/SNMP Management Card

Output

Output Power Capacity
16kW /20 kVA
Max Configurable Power
16kW /20 kVA
Nominal Output Voltage
230V
Output Voltage Note
Configurable for 220 : 230 or 240 nominal output voltage
Efficiency at Full Load
94%
Output Voltage Distortion
Less than 5%
Output Frequency (sync to mains)
50/60 Hz +/- 3 Hz user adjustable +/- 0.1
Crest Factor
3 : 1
Waveform Type
Sine wave
Output Connections
(1) Hard Wire 3-wire (H N + G)
(1) Hard Wire 5-wire (3PH + N + G)
(8) IEC 320 C19
(2) IEC Jumpers
Efficiency at Half Load
94%
Bypass
Built-in Static Bypass,Internal Bypass (Automatic and Manual),Optional External Bypass

 

Input

Nominal Input Voltage
230V
Input Frequency
40 - 70 Hz (auto sensing)
Input Connections
Hard Wire 3 wire (1PH+N+G)
Hard Wire 5-wire (3PH + N + G)
Input voltage range for main operations
160 - 280V
Other Input Voltages
220,240
Maximum Input Current
111A
Input Breaker Capacity
125A
Input Total Harmonic Distortion
Less than 5% for full load

 

Batteries & Runtime

Battery Type
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Included Battery Modules
4
Typical recharge time
2.50hour(s)
Replacement Battery
RBC44
RBC Quantity
4
Nominal Battery Voltage
+/-192 V (split battery referenced to neutral)
discharge_battery_voltage
+/-154 V
Efficiency in Battery Operation
93%
Typical Backup Time
at Half Load
15.3minutes (8000 Watts)
Typical Backup Time
at Full Load
4.9minutes (16000 Watts)
Runtime Chart
Smart-UPS RT
Extended Run Options
APC Smart-UPS RT 20kVA RM 230V

 

Communications & Management

Interface Port(s)
DB-9 RS-232,RJ-45 10/100 Base-T,Smart-Slot
Pre-Installed SmartSlotâ„¢ Cards
AP9619
Control panel
Multi-function LCD status and control console
Audible Alarm
Audible and visible alarms : configurable delays
Emergency Power Off (EPO)
Yes

 

Surge Protection and Filtering

Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449

 

Physical

Maximum Height
533.00mm
Maximum Width
432.00mm
Maximum Depth
773.00mm
Rack Height
12U
Net Weight
247.73KG
Shipping Weight
314.27KG
Shipping Height
990.00mm
Shipping Width
610.00mm
Shipping Depth
1003.00mm
Color
Black
Units per Pallet
1.00

 

Environmental

Operating Environment
0 - 40°C
Operating Relative Humidity
0%
Operating Elevation
0-3000meters
Storage Temperature
-15 - 45°C
Storage Relative Humidity
0%
Storage Elevation
0-15000meters
Audible noise at 1 meter from surface of unit
59.00dBA
Online Thermal Dissipation
3487.00BTU/hr

 

Conformance

Regulatory Approvals
EN/IEC 62040-2,EN/IEC 62040-1-1,VDE
Standard Warranty
2 years repair or replace

Reviews